Description
GENERAL
The M00FA122A is a analog automatic voltage regulator made by Marelli in Italy. Standard on 160- 225 frames. This regulator senses 2 phases and adjusts excitation when needed.
Auxiliary windings is needed to power the AVR.
APPLICATIONS
- Mainly used on Olympian, FG Wilson & Caterpillar CAT generator sets
CORRESPONDING, ASSOCIATED & OBSOLETE PART NUMBERS
- Marelli 11000013
- Marelli Mark VX
- Marelli M00FA122A
Technical Data
– Regulation Accuracy: +/- 0.5% steady state conditions
– Voltage Drift: +/- 0.5% voltage chage, for 50 ° C amb. temperature change
– Respond Time: 1 cycle (20ms – 16.6ms)
– Operating Temperature: -30 ° C ÷ 70 ° C
– Exciter Field Resistance: 8 Ω (min) ÷ 20 Ω (max)
– Supply Voltage: 170 -270 V (100/120Hz)
– Power Supply: 350 VA (max)
– Power Dissipated: 15 W (max)
– Voltage Sensing: 170 -270
– Output voltage (DC): 30 V
– Output Current (DC): 5 A (max, continuous)
– Output current (DC): 8 A (max one minute forcing)
Remarks:
– Delivery Schedule: 4 working days ex-warehouse upon confirmation of payment received. (Transit time not inclusive.) In the event of some unforeseen reason out of stock, please allow 2 to 3 weeks lead time.
– Receipt: Once the parcel pick up, we will notify you via email. Airway bill no. will be advise as well.
– Product Origin: Italy
– Shipping: All parts ship door to door via courier service. All taxes and duty fees at destination at buyer cost.
– Should you not able to add more quantity, which means the value exceed the libility cost. Please send us an email (info@thai-avr.com) to request for official quotation. We will respond to your enquiry asap.
| Model | Mark VX |
| Frame size | 160 ÷ 225 |
| Technology | ANALOGUE |
| Regulator | Mark VX |
| Part number | 11000013 |
| Compliance | CE and UL unlisted |
| Generator frame size | Standard 160÷225 |
| AVR supply | Auxiliary winding*, mains |
| Voltage sensing | Single phase |
| Voltage remote control | Arrangement |
| Radio interference supressor | Internal |
| MARK VX | 11000013 |
| Limiters | Under-frequency |
| Power supply voltage | 170 ÷ 277 Vac @ 50/60 Hz |
| Power supply source | Auxiliary windings, mains |
| Voltage build-up | 5 Vac |
| Voltage sensing type | 1-phase |
| Voltage sensing range | 170 ÷ 277 Vac |
| Maximum continuative field current | 0 ÷ 5 Adc |
| Maximum forcing field current | 0 ÷ 8 Adc |
| Maximum field voltage | 100 Vdc |
| Field resistance | 8 Ω ÷ 20 Ω |
| Regulation accuracy from no load to full load | ±0.5 % |
| Steady state accuracy | ±0.1 % |
| Accuracy with ±4% engine governing | ±1 % |
| Thermal Drift | ±0.5 % |
| Response time | 1 cycle |
| Operating temperature | -30°C ÷ +70°C |
| Storage temperature | -40°C ÷ +80°C |
| Interface | Potentiometers |
| Protection | Under-frequency limiter |
| Internal fuse, replaceable | |
| Control | External potentiometer, 100 kΩ – 1 W |
| External DC voltage signal (0-10 V) | |
| L | 160mm |
| B | 93.6mm |
| K | 137mm |
| H | 45mm |
| D | 5.5mm |
| Weight | 370g |